Near miss: Emergency fire pump could not be started from the bridge
A member has reported a near miss incident in which it was discovered that an emergency fire pump could not be started from the bridge. The discovery was made during a fire drill exercise on a vessel. The Master immediately informed the chief engineer. The chief engineer took action and noticed that the Emergency Fire pump main switch in the engine room was switched to local control. He switched it from local control to bridge remote and informed the bridge to start again; on this attempt it was started successfully and came on line.
Our member’s investigation noted the following:
- What went wrong? The vessel’s Emergency Fire pump main control switch in the engine control room was switched to “local control” instead of “remote/bridge control”. This meant that the Emergency Fire pump could not have been started from the bridge;
- Stop work authority (safety observation) was not properly used. The chief engineer confirmed that when he had joined the vessel he had found the main switch on local control but did nothing to correct it;
- Existing company procedures were not followed by the Master or the chief engineer, for monthly and weekly checks of this equipment. “Run the Emergency Fire pump on weekly basis and ensure that it is capable of supplying water under pressure to two charged fire hoses“. This item was marked as completed;
- There was a failure of communication: The fire drill scenario was particularly highlighted to the chief engineer, including the fact that during fire drill it would be required to start the Emergency Fire pump from the bridge. It was obviously understood but order and procedures were not followed.
Action:
- Chief engineer to ensure that the main switch in the engine room is always stationed on “Bridge Remote Control”. A sign or notice to this effect to be posted in the engine room to remind engineers to always leave the switch on bridge remote control.
Lessons learnt:
- Ask questions, be willing to exercise the stop work authority; don’t assume it’s all just business as usual;
- Drills and exercises exist for a reason – treat them seriously and guard against complacency;
- Ensure that critical equipment checklists and tests are thoroughly carried out for real, not just ticked off;
- Handovers at crew change and shift should be comprehensive and thorough, with a written record, and should cover all vital areas of concern.
Members may wish to refer to the following incident (search words: pump, switch)
Safety Event
Published: 21 March 2017
Download: IMCA SF 06/17
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.