UK HSE: Poorly maintained electrical installation caused fatality

The UK Health and Safety Executive prosecuted a warehouse management solutions company after an employee was fatally electrocuted while servicing electrical equipment.

What happened

A worker was carrying out pre-planned maintenance on an air compressor when he was electrocuted. He was not found for more than an hour following the incident. His injuries were fatal.

What went wrong?

Investigation found that:

  • Control measures in place to prevent contact with electricity during maintenance activities were neither suitable nor sufficient;
  • The electrical systems had not been tested or visually inspected since installation, and an incorrect isolating switch had not been identified.

The HSE inspector noted that “Poorly maintained electrical installations and faulty electrical appliances can kill or severely injure people; and cause damage to property.  This was a wholly avoidable incident, caused by the failure of the company to implement safe systems of work and identify the risks. Had the company identified the correct isolation point for the compressor and ensured that employees were sufficiently trained and supervised in the lock off procedures expected of them then this fatal incident would not have occurred.” (IMCA emphasis).

Press release here.

IMCA notes that appropriate control of electrical equipment is something worth looking closely at, particularly in two areas:

  • Where personnel using the equipment may not be engineers or electrical professionals (for example, the galley, the mess, the gym or other spaces not used for work);
  • Where access to electrical equipment or wiring is very difficult or is in spaces rarely visited by personnel.

Members may wish to refer to:

Safety Event

Published: 31 August 2021
Download: IMCA SF 24/21

Relevant life-saving rules:
IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.