Older “Norfolk Range” powder extinguishers from before 2009

The UK Health and Safety Executive (HSE) has published the following alert regarding a fault in older ‘Norfolk Range’ large dry powder fire extinguishers, manufactured in the United Kingdom before 2009. These extinguishers may be affected by moisture ingress at a threaded joint at the base of the unit, rendering the unit inoperable. The problem may not be identified during ‘routine’ service inspections.

Users should identify if their extinguishers are likely to be affected. If yes, and the extinguisher has been left exposed to adverse conditions since its last extended service, the condition of the elbow joint at the base of the unit should be examined by a competent service engineer.

If you are unsure if your extinguishers are affected by this safety alert, you may wish to consult your supplier.

More detailed information is available from the UK HSE: hse.gov.uk/safetybulletins/norfolk-large-wheeled-dry-powder-fire-extinguishers.htm

Type of large dry powder extinguisher affected
Type of large dry powder extinguisher affected

Safety Event

Published: 22 October 2015
Download: IMCA SF 16/15

IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.