Electric shock due to water in electrical equipment
What happened
There was an uncontrolled spraying of fresh water from a sounding pipe in the galley, resulting in electrical equipment getting wet. As a result someone got an electric shock. The incident occured during fresh water supply to a vessel, when the sounding pipe cap (located on the floor in the vessel galley) did not withstand the pressure, and so water sprayed out into the galley and onto the electrical stoves and deep fat fryer.
The flow of water was stopped and spilled water was mopped up, and the catering team continued to work. However, it appeared that water had penetrated the electrical circuitry of the deep fat fryer, and the steward received a mains electrical shock. This was reported, and the electrical equipment isolated. The steward was not harmed.


What were the causes?
- No-one had assessed the risks of a large volume of water spilling into the galley from the freshwater tank sounding pipes, nor considered the potential contact with electrical equipment;
- Drainage of the spilled water was delayed because the catering staff usually kept drainage system scuppers closed in the galley because of the smell coming out of the drainage system.
The actions
- The drainage system in the galley should be always kept open;
- Review, revise and update risk assessments as related to potential water flooding from the freshwater tank sounding pipes;
- Ensure the catering crew are kept informed of relevant inspection and maintenance requirements for their equipment.
Members may wish to refer to:
Safety Event
Published: 17 March 2021
Download: IMCA SF 08/21
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.