Electrician received electric shock
A member has reported an incident in which an electrician received an electric shock whilst working on faulty electrical equipment. The vessel electrician had been called to the gymnasium because the running machine had developed a fault and was no longer working.
The running machine had been purchased for the vessel in the USA and required a110v supply. A 220v/110v transformer had also been sourced in the USA and was mounted on the bulkhead next to the running machine, with a connecting cable into the vessel 220v supply.
During initial investigation of the fault, the electrician decided to remove the 220v supply cable from the transformer to allow testing to be completed. The electrician unplugged the supply cable from the transformer connection first, unaware that it had two male connections (the standard configuration is one male and one female connection to ensure live terminals are recessed). As he started to remove the connection from the transformer, his left hand came into contact with the exposed live pins and he received an electric shock.
After receiving the shock, the electrician fully unplugged the supply cable from the vessel 220v socket and reported the incident. He attended the vessel medic where he was given a thorough observation, no injuries were identified and no further treatment was required.
An investigation revealed the following:
- Poor work practice and inadequate risk assessment for electrical isolations;
- There was a poor level of hazard awareness and task planning prior to starting work;
- Good practice is that electrical supply cables should be isolated from the power supply prior to testing;
- Design deficiencies of the electrical equipment that was being installed and used on the vessel were not identified;
- It should not be assumed that equipment purchased for the vessel is fit for purpose until it has been correctly checked and all potential hazards have been identified, risks assessed and any mitigating actions put in place;
- Electrical equipment purchased for the vessel should not be utilised until a full risk assessment has been conducted and all relevant mitigating safety actions have been completed.
Actions taken included the following:
- Ensure electrical equipment onboard has the correct connections, configuration and rating for safe use;
- Ensure that all electrical equipment purchased for the vessel is fully inspected and tested and a full risk assessment of its intended use takes place prior to installation and use.
Safety Event
Published: 27 July 2011
Download: IMCA SF 08/11
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.