Fire in diesel generator following tests
What happened
There was a small fire in the engine room on a vessel in port. The incident occurred when a diesel generator was being maintained by a third-party maintenance team. On completion of a change of alternator bearings, the generator was tested at idling speed, and no problem was found. But when the generator was tested at operational speed, after a few minutes fire came out of the non drive end exciters. The alarm was raised; the diesel generator was brought to an emergency stop and the fire was put out with an extinguisher.

What went wrong
There was a misalignment of the internal cover of the non drive end bearing. This misalignment caused friction against the shaft and subsequent sparking. The root cause was considered to be insufficient supervision of the third-party personnel conducting the maintenance.
Lessons
- Whilst there was only a burnt alternator in this case, the potential was for the fire to have spread throughout the engine room;
- Ensure full and thorough supervision of the personnel of third-party contractors;
- Check carefully the status and readiness of any equipment after maintenance and test – in this case, it was as well that they tested it at operational speed rather than only when idling.
Members may wish to refer to
- Engine room fire on a ferry [bearing failure and a fire caused by friction]
- Fire alarm activation in engine room
- Near Miss: Fire blanket caught fire during third-party hot work
- Small fire following hot work
Safety Event
Published: 24 July 2023
Download: IMCA SF 18/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.