Fire in ROV workshop
What happened?
A crew member noticed smoke coming from the ROV workshop and reported a fire.
What went right?
- There was no panic, and the fire response team was ready at short notice;
- The communications system was used clearly and effectively;
- The training, experience and action of the fire response team, and the crew, prevented further damage that could have significantly exceeded the actual damage, and even jeopardised the ship itself.

What went wrong?
- A rechargeable headset flashlight was left on charge unsupervised, also on a UPS supply.
Lessons learned
- The importance of checking the condition of all personal electrical equipment;
- All electrical appliances should be sourced from a reputable supplier and should be in good working condition;
- Plug sockets and extension leads should be used correctly and not overloaded;
- Charger cords for all electronic devices should be in good working condition (with no exposed wiring) prior to being brought offshore, and likewise, sourced from a reputable supplier;
- Charging devices should not be left on surfaces that are potentially flammable or that can promote heat build-up;
- Avoid leaving charging cables or portable electronic devices on bedding;
- Remove electronic devices from chargers and outlets once fully charged;
- Include information about the hazards of charging portable devices during orientations and post relevant signage in living quarters.
Members may wish to refer to:
Safety Event
Published: 30 October 2023
Download: IMCA SF 25/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.