Fire in the laundry room
What happened?
A smoke detector was activated. A deck officer checked the origin of the alarm which was coming from an area close to the laundry room. A general fire alarm was sounded; all personnel started to muster, and a firefighting team assembled.
The fire team found the source of the fire which was coming from an industrial tumble dryer in the laundry room. The fire was safely extinguished before the personnel muster was complete.

What went right
- Everyone started to muster quickly and professionally;
- The fire fighting team responded to the action area and put out the fire.
What went wrong
Our member noted that in this case:
- The air flow of the tumble dryer heating system may have allowed flammable material (particulate) to be conveyed through the electrical heating elements and pushed into the drum containing the clothes. The electrical elements are not protected (isolated) and are positioned very close to the actual rotating drum;
- The dryer had undergone recent maintenance (troubleshooting) and the control panel and set-up parameters had been changed during this process, and were different from the original;
- There was no smoke detection in the laundry – only heat detectors – and the alarm was by the smoke detector adjacent the door of the laundry in the corridor because the door was partially open;
- The type of tumble dryer conformed to no known industrial standard.
What were the causes
- Changes to the dryer in the troubleshooting/maintenance process;
- Lack of smoke detection in the laundry.
Lessons and actions
- Use equipment complying with a recognized industrial design standard;
- Use spare parts that are either original and/or fully compatible with the equipment;
- Review fire/smoke detection system to identify potential improvements particularly in laundry area.
Members may wish to refer to
Safety Event
Published: 16 October 2023
Download: IMCA SF 24/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.