Flash fire on Oxygen gas quad hose
What happened
There was a flash fire on an Oxygen hose line onboard a DSV. The incident occurred during routine checks, when an LST (Life Support Technician) reported that the Oxygen supply pressure to dive control was low (25 Bar). SAT control informed Dive Control and agreed that a new Oxygen supply was required. The LST went to the appropriate quad (on the main deck), and started by closing the row of eight bottles of Oxygen before opening a new row. Whilst opening the new row of Oxygen supply bottles the LST heard an unfamiliar noise (a flapping sound from the regulator) and immediately closed the cylinder pillar valve and closed the valve on both regulators (SAT control and reclaim regulator valve) and quickly moved away from the Oxygen quad. The LST immediately returned to SAT control and reported to his supervisor.
Shortly afterwards, the Oxygen hose burst followed by an explosion and flash fire at the reclaimed Oxygen hose line. The deck foreman who investigated the source of the explosion immediately extinguished the fire with a dry powder fire extinguisher. There was no damage found on the nearby gas quads apart from the affected hose and regulator.




What went wrong – investigation findings
Investigation showed that the bullnose inlet (connection to the pillar valve) had no filter to stop rust contaminant from the cylinder going into the regulator. Small particles of rust from inside the cylinder accumulated inside the regulator causing high friction after the Oxygen release, resulting in heat and contributing to the spark, explosion and fire.
Members may wish to refer to:
Safety Event
Published: 20 July 2022
Download: IMCA SF 18/22
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.