Hazard hunt: fire dampers and fixed firefighting systems
What happened?
A member reports four recent Port State Control detentions for its vessels; two of which related to fire safety, fire dampers and fixed firefighting equipment. In one incident, the fire dampers for four engine room ventilation fans were found to be faulty. On the same vessel, the manual isolation valve for the low-pressure CO2 firefighting system was found to be in a closed position. Crew would not have been able to deploy the CO2 firefighting system into protected spaces from the remote location. Additionally, the wrench used to open the manual isolation valve was not present in the local control area.








What lessons were learned?
- Check that fire dampers are free of damage and corrosion;
- Check that fire dampers are clearly marked including open and closed positions;
- Ensure fire dampers are easy to operate;
- Ensure flame screens are in good condition;
- All operating handles, wires and stoppers should be in good working condition;
- All such equipment should be regularly inspected and maintained as part of a planned maintenance system;
- Crew should be familiar with the operation of fire dampers and this familiarity should be checked regularly with drills.
Members may wish to refer to:
Safety Event
Published: 12 March 2019
Download: IMCA SF 04/19
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.