Skip to content

Helideck foam sample

Further to information provided in information note Firefighting foam on helidecks, we have been provided with the following information arising from a foam sample test onboard a vessel with a helideck.

The company reports that the results from a sample from the helideck foam monitor tank submitted for testing were perplexing. They stated that the foam had a very high concentration of water, as opposed to 0%.

Investigations were carried out onboard to comprehend this high concentration of water in the foam sample. After various tests it was concluded that the non-return valve located between the foam tank and pipework from the pump to the helideck foam monitor had been leaking.

This was not immediately noticed. However, the consequences of this could have been devastating – should a helicopter fire on the helideck have occurred, the vessel would have been using a mixture of foam concentrate and water which was incapable of producing the required blanket of foam.

The company concerned has instructed its helideck-equipped vessels to take the following measures to prevent recurrence of this:

  • Where possible, test non-return valves for leakage;
  • Enter the non-return valve item into the vessel’s planned maintenance system for inspection and testing on a frequent basis when convenient;
  • Schedule to fit an isolation valve between the foam tank and non-return valve.

Safety Event

Published: 1 January 2005
Download: IMCA SF 01/05

IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.