Inappropriate automatic activation of fixed fire-fighting system
What happened
The fixed firefighting system in the engine room on a harbour tug automatically activated and all the gas in the tanks emptied. This occurred after two consecutive blackouts on the tug within 24 hours. No-one was harmed.
What went wrong
- It was discovered that the firefighting system was activated by a sudden rise in battery voltage following the malfunction of the solenoid valve on the pilot cylinder, after the blackout;
- Our member considered that the low voltage (24v) electrical system in the tug may not have sufficient power to supply the critical equipment it was being used for;
- There was a lack of indication on the bridge or in the engine room regarding the operation of the electrical system; it was not possible to discern whether it was in emergency mode or normal operational mode.

Lessons to learn
- Check the functionality of vessels’ general emergency response systems:
- Review the ships’ electrical system, especially systems affecting critical equipment – is there sufficient current supplied to operate the system in all cases?
- Review blackout and emergency drill protocol in case of loss of power;
Members may wish to refer to:
- Inadvertent activation of condensed aerosol fire extinguishing system leads to a fatality
- Wrong key for the CO2 room
- MAIB: Blockage of fixed CO2 fire extinguishing system pilot hoses
Members may wish to review the incident of the cargo vessel Dali hitting and destroying the bridge in Baltimore. A Vessel blackout may have been one of the causal factors. IMCA hopes to make a safety flash on this incident available when a full report with findings is published.
Safety Event
Published: 14 October 2024
Download: IMCA SF 20/24
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.