Skip to content

Near miss: fire/explosion thermal runaway – lead acid battery

What happened?

An overheated and swollen lead acid battery was found on-board a vessel.

What went wrong?

When charging, the temperature inside the affected battery rose beyond the critical level.  As the heat was unable to dissipate fast enough, the chemical reaction inside the battery accelerated and led to an even higher charging current and heat generation.

What were the causes?

Heat generated in the battery cell had occurred without any warning signs:

  • The battery in question was found to be at the end of its design life and vulnerable to thermal runaway;
  • Due to the heat generated within the battery, the battery became pressurised and deformed;
  • In addition to design life, overcharging, internal physical damage, internal short circuit or a hot environment are all potential causes for battery fires or explosions.

What actions were taken?

  • Depending on the battery configuration; isolate the battery or string of batteries, or shut down the charger;
  • Cool the battery and ventilate the room.

What lessons were learned?

  • Ensure all batteries are subject to periodical inspection and maintenance; consideration may be given to inspection by infra-red camera to look for hotspots;
  • Report any sign of external damage;
  • Ensure that battery chargers and procedures are correct for the battery type;
  • Consider the installation of a “thermal runaway monitor” on battery packages (UPS);
  • Batteries should be in rooms suitable for batteries with the required ventilation, fire detection and fire-fighting capabilities;
  • Ensure there is a specific risk assessment and transport/disposal plan relating to the removal of faulty batteries, with specific care being taken to identify the correct personal protective equipment (PPE) to be worn, and any transportation necessary.

Members may wish to refer to the following incidents (all relating to lead-acid batteries):

Safety Event

Published: 12 August 2019
Download: IMCA SF 19/19

Relevant life-saving rules:
IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.