Sludge Accumulation in Fresh Water Tank
During inspection of a fresh water tank, it was discovered that there was significant sludge accumulation in the tank. Based on the condition of the tank, it was seen as more than likely that other tanks would be similarly affected and that the cause was due to a common source of water. Sludge build-up in fresh water tanks, hoses and pipes can lead to the prevalence of bacteria that may pose a health hazard.
What went wrong
Our member understood that the condition was as a result of the quality of the water obtained from port. There was an accumulation of sedimentation and of organic and inorganic matter over a period of time.
Actions
- Immediate inspection of other fresh water tanks to ensure potability of water supply, and subsequent maintenance (taking note of the requirement for Confined Space Entry permits to work) was arranged as soon as reasonably practicable;
- Internal tank inspection for signs of possible contamination and debris every 6 months for potable water and every 12 months for non-potable water;
- Disinfection of hoses as a routine measure every 6 months, or whenever any contamination is suspected. Our member flushed hoses thoroughly through and completely filled them with a solution of 50 ppm residual free chlorine, which was then allowed to stand for a period of at least 1 hour before the hoses were emptied and re-stowed.

Members may wish to refer to:
- Two cases of contaminated drinking water
- Suspected case of Legionella onboard vessel
Safety Event
Published: 23 February 2021
Download: IMCA SF 06/21
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.