Sparks from funnel caused small fire
What happened?
A small fire was detected on the well deck area of a diving support vessel (DSV). This occurred during diving operations whilst the vessel was in DP3 mode.
The fire was extinguished by the Bosun, using two foam extinguishers. There was no injury to personnel or damage to equipment.
The correct protocol was followed by vessel personnel – activation of manual fire alarm and muster of all personnel; an amber light given to dive control (together with verbal warning of fire). The dive supervisor then ordered divers back to the Bell.
What went wrong?
The fire resulted from sparks which fell from the starboard funnel into the well deck area and ignited a 1 tonne gabion sack containing cardboard (which was being stored for onshore recycling).
What were the causes?
- A build-up of soot in the exhaust system, caused by prolonged operation of vessel engines in low load;
- Lack of maintenance routine for clearing of soot within the system.
What actions were taken?
- Extensions installed onto drain plugs to provide easier access for planned maintenance activities;
- As a secondary precaution, gauze type spark arrestors manufactured and installed on top of each exhaust stack;
- Update planned maintenance regimes, with regard to the cleaning of soot collectors and routine checks for soot removal.
Members may wish to refer to:
Safety Event
Published: 12 March 2019
Download: IMCA SF 04/19
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.