Skip to content

USCG Homeport Marine Safety Alert: Recent failures of dynamic positioning (DP) systems on MODUs

The United States Coast Guard has recently issued the attached Marine Safety Alert about recent failures of dynamic positioning systems on mobile offshore drilling units.

Clarification has been sought on the following recommendations from the safety alert:

  • Where ride-through capability is an essential part of the DP redundancy concept, it should be proven by live short circuit and ground fault testing.
  • Perform regular thermal imaging surveys of DP system electrical equipment (e.g. switchgear, drives, motor controllers, etc.) as part of a preventative maintenance program to provide early detection of faulty or loose connections.

The response, which should be noted, was:

  • Guidance does state that analysis and proper planning is required to undertake short circuit testing;
  • The intent is to do this not at FAT, but on the vessel, with appropriate planning and safety precautions;
  • Additional guidance is provided in the Marine Technology Society Techop guidance;
  • One of the objectives is to have the test validate the model, so that subsequent testing can be done with analytical and modelling techniques based on a validated model;
  • Any short circuit testing is to be accompanied by the proper planning and with appropriate risk mitigating measures in place.

The safety flash draws attention to the Marine Technology Society’s operational guidance which is available from the MTS dynamic positioning website www.dynamic-positioning.com. It should be noted that this guidance refers extensively to IMCA guidance.

We would also like to draw attention to the guidance contained within Offshore vessel high voltage safety.


IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.